Publication 1757-PM002A-EN-E - June 2006
RSFieldbus Remote Access B-3
Remote RSView SE OPC
Access
The architecture for this scenario is shown below. While this can be performed
on both Windows 2000 and XP, this scenario is completed in Windows 2000.
You must perform two different configurations to be able to connect through
DCOM: the Client-side and the Server-side.
Server and Client DCOM Settings
Complete the following on both the Server and the Client.
1. Click Start Run.
2. In the Open field, enter <dcomcnfg> and click OK.
3. Select the Default Properties tab and select the following:
a. Enable Distributed COM on this computer
b. Default Authentication Level: Connect
c. Default Impersonation Level: Identify
4. Select the Default Security folder and click Edit Default under Default
Access Permissions.
RSFieldbus
RSView SE
Windows 2000 SP4
1757-FFLD
STATUS
WDOG
BATT
NS 1
MODE
H1
H1
H1
H1
H1-1
H1-2
H1-3
H1-4
FOUNDATION Fieldbus
FOUNDATIO N Fieldbus
Linking Device
RSFieldbus
Windows 2000 SP4
Server
Client
HSE Network TCP/IP