FLEX I/O Isolated Input HART Analog Module 23
Publication
1794-IN115C-EN-P - April 2009
Status Indicator
The OK status indicator is bicolor, red, and green. The indicator
flashes green for these reasons:
• The module configuration word is zero (for example,
powerup reset condition).
• The 24V DC user power is off.
• The module is in Configuration mode.
The indicator displays red to indicate the module did not pass the
initial hardware test. Recycle power in response to this display.
After powerup, if the status indicator is not flashing green or solid
green, recycle module power to verify a proper reset of the bus
interface.
Specifications
FLEX I/O 8-input Isolated HART Module - 1794-IF8IH
Attribute Value
Number of inputs 8 isolated
Module base Catalog numbers 1794-TB3, 1794-TB3S
Resolution 16 bits - unipolar; 15 bits plus sign - bipolar
Current 0.320 µA/cnt unipolar; 0.640 µA/cnt bipolar
Data format
Engineering Units
(4)
Percent of Full Scale
Proportional Count
Conversion type Sigma Delta
Update rate see input update rate table
Input current terminal 4…20 mA (user configurable)
0…20 mA (user configurable)