Chapter 4
Application Information
4–6
Discrete Inputs to the PLC–5
The discrete inputs to the PLC–5 are as follows:
T
able 4.3
Octal
Bit
Number
Decimal Bit
Number
Input Description State Values
17 15 Module Status 1 = Module Failed
16 14 Raise Voltage 1 = Raise
15 13 Lower Voltage 1 = Lower
14 12 Raise Speed – Frequency Adjust 1 = Raise
13 11 Lower Speed – Frequency Adjust 1 = Lower
12 10 Raise Speed – Phase Adjust 1 = Raise
11 9 Lower Speed – Phase Adjust 1 = Lower
10 8 Raise Power – Load Share Adjust 1 = Raise
7 7 Reserved N/A
6 6 Reserved N/A
5 5 Reserved N/A
4 4 Reduce Power – Load Share Adjust 1 = Lower
3 3 Close Breaker 1 = Close Breaker
2 2 Synchronization Failure 1 = Failure
1 1 Powered Up Bit 1 = Module Ready
0 0 Reserved N/A
The Module Status discrete input to the PLC–5 when set to 1 indicates that
the LSM has identified a potential problem. A value of 0 indicates normal
operation of the LSM. Additional information pertaining to the cause of the
problem may be obtained by reading the appropriate block transfer data from
the “Diagnostic Parameters” Table B.11. (See Appendix B, “Block Transfer
Tables and Discrete I/O Definition”, for additional information.)
If the Module Status discrete input to the PLC–5 is set to 1, all block transfer
writes will be ignored and only the Diagnostic Parameters block transfer read
will return valid data. Any other block transfers should not be executed at
this time.
The Raise Voltage synchronization error discrete input to the PLC–5
indicates that the Synchronizing Bus has a lower voltage level than that of
the Reference Bus.
The Lower Voltage synchronization error discrete input to the PLC–5
indicates that the Synchronizing Bus has a higher voltage level than that of
the Reference Bus.
The Raise Speed – Frequency Adjust synchronization error discrete input to
the PLC–5 indicates that the Synchronizing Bus is producing voltage at a
frequency lower than that of the Reference Bus.
Int
erf
acing
to
t
he
LSM
C
ontinu
ed