A
A
WARNING
CONTACT WITH ENERGIZED EQUIPMENT CAN
RESULT IN DEATH, SEVERE PERSONAL INJURY,
OR
SUBSTANTIAL PROPERTY DAMAGE. DO NOT
ATTEMPT TO INSTALL
OR
PERFORM
MAINTENANCE ON EQUIPMENT WHILE IT
IS
ENERGIZED. ALWAYS VERIFY THAT NO VOLTAGE
IS
PRESENT BEFORE PROCEEDING WITH THE TASK,
AND ALWAYS FOLLOW GENERALLY ACCEPTED
SAFETY PROCEDURES.
ALLEN-BRADLEY
IS
NOT LIABLE
FOR
THE
MISAPPLICATION
OR MISINSTALLATION
OF ITS
PRODUCTS.
The user is cautioned to observe all recommendations,
warnings, and cautions relating
to
the safety of personnel
and equipment as well as all general and local health and
safety laws, codes, and procedures.
The recommendations and information contained herein
are based on Allen-Bradley experience and judgement,
but should not be considered to be
all-inclusive or cover
-
ing every application or circumstance which may arise. If
any questions arise, contact Allen-Bradley for further
information or instructions.
1.
INTRODUCTION
Fig.
1
-
1
Shunt Trip Installed in
Q
-
Frame
Circuit Breaker
GENERAL INFORMATION
The shunt trip (Fig.
1
-
1)
provides remote controlled elec
-
trical tripping for the circuit breaker.
It
consists of an inter
-
mittent rated solenoid with a tripping plunger and a cutoff
switch attached
to
a plug
-
in module. The plug
-
in module
is mounted in
slots
in the top
of
the trip unit and occupies
the accessory cavity in the circuit breaker frame. When
the solenoid is energized, the plunger extends and
presses against an intermediate plunger which operates
the trip bar in the trip unit.
As
the circuit breaker trips, the
molded crossbar presses against the cutoff switch oper
-
ating arm to open the cutoff switch, disconnecting power
to
the solenoid and preventing coil burn out.
40752-075(1) Effective 4/02
Q and M-Frame Circuit Breakers
Instruction Leaflet for Shunt Trip
Bul. 140U
Vista de pagina 0
1 2 3 4 5 6 7 8

Indice de contenidos

Pagina 1 - WARNING

A A WARNING CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE. DO NOT ATTEMPT TO INSTALL OR

Pagina 2

Page 2 a WARNING IF ENERGY IS APPLIED TO SHUNT TRIP LEADS, DO NOT ATTEMPT TO RESET AND CLOSE THE CIRCUIT BREAKER. ATTEMPTING TO CLOSE THE CIRCUIT B

Pagina 3 - WARN IN G

Page 3 A CAUTION LEADS SHOULD BE FORMED AND ROUTED TO CLEAR ALL MOVING PARTS WHEN ACCESSORY IS PROPERLY INSTALLED. PIGTAIL WIRES COULD BE DAMAGED IF I

Pagina 4 - 40752-075(1) Effective 4/02

Page 4Fig. 2-1 Shunt Trip Kit I Rear Exiting Leads (Preferred) Side Exiting Leads Terminal Rlock Opposite-Side Exiting Leads Fig. 2-2 Accessory Wiring

Pagina 5

Page 5 ~ Flat Blade Screwdriver Fig. 2-4 2-8. Place accessory labels (supplied with kit) on circuit breaker. (See Fig. 2-5.) Note: Accessory labels s

Pagina 6 - 40752-075(1)

Page 6 40752-075(1) Effective 4/02Pigtail Leadsr---- ----- -------7I IIFig. 2-6. Shunt Trip Connection Diagram

Pagina 7

Page 7 TABLE 1-1. SHUNT TRIP ELECTRICAL RATING DATA Average circuit breaker contact total opening time approximately 6 milliseconds, depending on volt

Pagina 8

Page 8 40752-075(1) Effective 4/02Printed in U.S.A./TQC