Digital I/O Conversion Module
(Cat 1492-CM1771-LD003)
I. Description
This Digital I/O Conversion Module provides for the conversion of (1) 1771, 32 point I/O modules to be converted to (1)
1756, 32 point I/O module and consists of the following:
(1) 1771 Module (32pt) to (1) 1756 Module (32pt)
(2) Conversion Modules: 1492-CM1771-LD003
(1) Cable: 1492-CONCAB005Z (Table 2, Section III)
(1) Conversion Mounting Assembly: 1492-MUA… (Table 1, Section II)
This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing
1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the 1492 Cable
is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the 1756 I/O
module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion Module and the 1492
Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V. As standard, both
portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2,
Section III for further details.
PN-114275
DIR 10000060086 (Version 01)
Publication 1492-IN033B-EN-E
Printed in U.S.A.
Conversion Compatibility and
Product I.D. Label
37-Pin Connector for cable 1492-CONCAB
Z
De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O
Chassis, and the power to the 1771 I/O Chassis itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.
WARNING
1492-CM1771-LD003 Conversion Module
Vista de pagina 0
1 2 3 4 5 6

Indice de contenidos

Pagina 1 - (Cat 1492-CM1771-LD003)

Digital I/O Conversion Module(Cat 1492-CM1771-LD003)I. DescriptionThis Digital I/O Conversion Module provides for the conversion of (1) 1771, 32 point

Pagina 2 - II. Installation

(2)II. InstallationThe 1492 Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see Table 1 below). A complete System Instal

Pagina 3 - III. Compatiblity

(3)III. CompatiblityFoot Notes: To understand any issues concerning I/O module compatibility, refer to the Installation Manuals for the specific 1771

Pagina 4 - V. Wiring Diagrams

(4)PN-114275DIR 10000060086 (Version 01)Publication 1492-IN033B-EN-EV. Wiring Diagrams1771-WN Swing ArmFrom 1771-IANThere are several key application

Pagina 5

1771-WN Swing ArmFrom 1771-IBNV. Wiring Diagrams (Continued)There are several key application considerations and system specifications (bottom of draw