150-SM6 Switch Position Identification:
The following defines the functions of the 5 Rotary Switches:
S1 = Initial Torque Configuration:
S2 = Current Limit Configuration:
S3 = Ramp Time Configuration- Starting:
Rotary Switch S1 Position Setting Resulting Initial Torque Value (in % Motor Torque)
0 10
1 16
2 22
3 28
4 34
5 40
6 46
7 52
8 58
9 64
A 70 (Default)
B 76
C 82
D 88
E 94
F 100
Rotary Switch S2 Position Setting Resulting Current Limit Value (in % Motor FLC)
0 200
1 220
2 240
3 260
4 280
5 300
6 320
7 340
8 360 (Default)
9 380
A 400
B 420
C 440
D 460
E 480
F 500
Rotary Switch S3 Position Setting Starting Ramp Time (in Seconds)
0 0.1
1 2
2 4
3 6
4 8
5 10 (Default)
6 12
7 14
8 16
9 18
A 20
B 22
C 24
D 26
E 28
30
S4 = Stop Time Configuration:
Rotary Switch S4 Position Setting Stop Time (in Seconds 1 )
0 Coast to Stop (Default)
1 2
2 4
3 6
4 8
5 10
6 12
7 14
8 16
9 18
A 20
B 22
C 24
D 26
E 28
F 30
F
1) When the “Braking” STOP MODE is selected (Device Configuration Bank Switch #3 and #4) the controller multiplies the selected “Stop Time” by 10.
Refer to Device Configuration Switch Bank.