14 Rockwell Automation Publication 150-QS002B-EN-P - October 2011
Quick Start
Factory Default Settings
The SMC Dialog Plus controller is pre-programmed with the settings listed in
the table below.
Saving Programmed Values to Memory
After you have programmed the controller settings you must save them to the
controller’s memory. To do this, follow the steps below:
1. Scroll to Parameter Mgmt. This is the last parameter provided in the Basic
Setup, Advanced Setup, and Calibrate programming groups.
2. Select the Store In EE option.
3. Press Enter.
Calibration
For current measurement accuracy, use the procedure below to calibrate the SMC
Dialog Plus controller to the connected motor. A clamp-on ammeter, which
provides a true rms measurement and has a published accuracy of ±1% (Fluke
model 33 or equal), is required to perform this procedure.
Parameter Setting
Starting Mode Soft Start
Ramp Time 10 seconds
Initial Torque 70% of locked rotor torque
Kickstart Off
Energy Saver Off
Stall Off
Phase Rebalance Off
Auxiliary Contacts Normal
Service Factor 1.15
Overload Class Off
Line Voltage 480 volts
Motor FLC 1.0 amps
Motor HP Rating 0.0 HP
Motor Code Letter G
ATTENTION: Overload protection in the SMC Dialog Plus controller is
disabled from the factory. The user must program the desired overload
trip class and motor full load current rating to achieve proper protection
IMPORTANT
If control power is removed from the SMC Dialog Plus controller before
you store the programmed values to memory, all programmed values will
be lost.