System Commissioning and Software Installation 7-3
1500-IN057C-EN-P June 2013
5. Use RSNetworx for DeviceNet to program and configure devices
(e.g., full load current, acceleration rate, etc.).
Do not download to a device before uploading from that device.
Otherwise, the node and baud rates will be overwritten, requiring
each device to be individually manually reprogrammed.
Make sure to set communication-loss behavior for each device.
I M P O R T A N TI M P O R T A N T
RSNetworx for DeviceNet can also be used to change
baud rates and node numbers, but remember that the
devices are normally pre-programmed at the factory.
6. Use RSNetworx for DeviceNet to program the DeviceNet scanner (if
required).
I M P O R T A N TI M P O R T A N T
When using a 2100-GK61 communication module,
keep in mind that there are two extra bytes of receive
data for the inputs on the 2100-GK61. Make sure the
number of bytes in the scanner configuration
corresponds with the number of bytes in the device.
See the 2100-GK61 user manual (publication 2100-
UM001_-EN-P, chapter 4) for more details.
7. Write the PLC program (if required).
8. If IntelliCENTER software is provided, load per the IntelliCENTER
Software User Guide (Publication 2100-UM002_-EN-P).