Installation InstructionsPOINT I/O Input ModulesCatalog numbers 1734-IB2, 1734-IB4, 1734-IB8, Series CTable of ContentsTopic PageImportant User Inform
10 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Remove a Mounting BaseTo remove a mounting base, you must remove any installed
POINT I/O Input Modules 11Publication 1734-IN051H-EN-E - April 2013Communicate with Your ModuleI/O messages are sent to (consumed) and received fr
12 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Wire the Module 24VDCSinkInputModule StatusNetwork Status1734IB201NODE:24VDCSin
POINT I/O Input Modules 13Publication 1734-IN051H-EN-E - April 2013Wiring for 1734-IB2 – Sink InputWARNING: If you connect or disconnect wiring wh
14 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Wiring for 1734-IB4 – Sink InputChannel Input Common Voltage0046115722463357Con
POINT I/O Input Modules 15Publication 1734-IN051H-EN-E - April 2013Wiring for 1734-IB8 – Sink InputNote: When connecting more than one wire in a t
16 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Wiring Example for 1734-IB8 Using 2-Wire Proximity SwitchesSystemPowerDeviceNet
POINT I/O Input Modules 17Publication 1734-IN051H-EN-E - April 2013Wiring Example for 1734-IB8 Using 3-Wire Proximity SwitchesSystemPowerDeviceNet
18 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Interpret Status IndicatorsRefer to the following diagram and table for informa
POINT I/O Input Modules 19Publication 1734-IN051H-EN-E - April 2013Indicator Status for ModulesStatus DescriptionModule status Off No power applie
2 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Important User InformationSolid-state equipment has operational characteristics
20 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013SpecificationsPOINT I/O Input Module – 1734-IB2, 1734-IB4, 1734-IB8Attribute Va
POINT I/O Input Modules 21Publication 1734-IN051H-EN-E - April 2013Indicators, module status 1 green/red, logic sideIndicators, input status 1734-
22 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Environmental SpecificationsAttribute ValueTemperature, operating IEC 60068-2-1
POINT I/O Input Modules 23Publication 1734-IN051H-EN-E - April 2013CertificationsCertification (when product is marked)(1)Valuec-UL-us UL-listed I
Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellau
POINT I/O Input Modules 3Publication 1734-IN051H-EN-E - April 2013Environment and EnclosurePreventing Electrostatic DischargeATTENTION: This equip
4 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013North American Hazardous Location ApprovalThe following information applies when
POINT I/O Input Modules 5Publication 1734-IN051H-EN-E - April 2013European Hazardous Location ApprovalThe following applies when the product bears
6 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Before You BeginYou can use these Series C POINT I/O™ Input Modules with DeviceN
POINT I/O Input Modules 7Publication 1734-IN051H-EN-E - April 2013About the ModuleThe POINT I/O sink input modules are available in two-input, fou
8 POINT I/O Input Modules Publication 1734-IN051H-EN-E - April 2013Install the ModuleThe module can be installed before or after base installation.
POINT I/O Input Modules 9Publication 1734-IN051H-EN-E - April 2013Install the Removable Terminal BlockA Removable Terminal Block (RTB) is supplied