POINT I/O Protected Sink Output Module 17
Publication
1734-IN585C-EN-E - December 2005
Channel
Number
Output
Termina l
Common Terminal Power
Channel 0 0 Common is daisychained
from either a 1734 adapter,
1734-FPD, 1734-EP24DC, or
from a user-supplied
external terminal block.
The 24V dc power for the
module is supplied by the
internal power bus and
originates from the same
adapter, 1734-FPD, or
1734-EP24DC as common.
Channel 1 1
Channel 2 2
Channel 3 3
Channel 4 4
Channel 5 5
Channel 6 6
Channel 7 7
Module power is supplied from the internal power bus.
Out 0
Out 1
Out 3
Out 2
Load
Load
42015
Load
C
ommon must be daisychained from a 1734 adapter, 1734-FPD, 1734-EP24DC, or from a
u
ser-supplied external terminal block. The 24V dc power to the module is supplied by the internal
p
ower bus and comes from the same 1734 adapter, 1734-FPD, or 1734-EP24DC as common.
1734-OV8E
0
2
6
3
1
7
4
5
Load
Load
Load
Load
Load
Out 4
Out 5
Out 7
Out 6
V
V