10 ArmorPoint I/O Modules with 8 Configurable 24V DC Points
Publication
1738-IN026B-EN-E - February 2010
In RSLogix5000, the default tag will be AdapterName:SlotNumber:O.Data.
The data type is a SINT.
In RSLogix5000, the default tags will be:
• AdapterName:SlotNumber:C.FilterOffOn
• AdapterName:SlotNumber:C.FilterOnOff
Default Data Map – Product Assembly Instance 34
Message Size: 1 Byte
76543210
Data Pt 07 Pt 06 Pt 05 Pt 04 Pt 03 Pt 02 Pt 01 Pt 00
Where: Pt = state of the output point
Default Data Map – Product Assembly Instance 103
Message Size: 8 Bytes
76543210
Data [0] Group Off2On Input filter
Data [1]
Data [2] Group On2Off Input filter
Data [3]
Data [4] FltM 7FltM 6FltM 5FltM 4FltM 3FltM 2FltM 1FltM 0
Data [5] FltV 7FltV 6FltV 5FltV 4FltV 3FltV 2FltV 1FltV 0
Data [6] IdIM 7IdIM 6IdIM 5IdIM 4IdIM 3IdIM 2IdIM 1IdIM 0
Data [7] IdIV 7IdIV 6IdIV 5IdIV 4IdIV 3IdIV 2IdIV 1IdIV 0
Where: Filter = 0 to 65000 us (0 = default)
Filter = 0 to 65535 us (1000 = default)
FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON)
IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)
IdlV = Idle Value (0 = OFF (default), 1 = ON)