Publication 1734-UM016A-EN-P - October 2010
1734/1738 I/O Module Assembly Information 37
Two-channel Discrete Output Modules with Status
All two-channel "enhanced" discrete output modules use the same
configuration and I/O assemblies. Use the tables shown below for the
following modules:
• 1734-OB2E or 1738-OB2E
• 1734-OV2E or 1738-0V2E
• 1734-OB2EP or 1738-OB2EP
Produced Input Data Assembly 4
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0
Configuration Assembly Instance 123
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Fault State 1 Fault State 0
1 Reserved Fault Value 1 Fault Value 0
2 Reserved Idle State 1 Idle State 0
3 Reserved Idle Value 1 Idle Value 0
4 Reserved Enable No Load 1 Enable No Load 0
5 Reserved Reset mode 1 Reset mode 0
6 Reserved Enable Latched Alarms 1 Enable Latched Alarms 0
7 Pad
Produced Input Data Assembly 42
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 Reserved Ch 1
Status
Ch 0
Status
Consumed Output Data Assembly 32
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 Reserved Ch 1 Ch 0