Publication 1738-IN012B-EN-E - August 2013
ArmorPOINT I/O 5V DC Encoder/Counter Module, Series A 15
Specifications
Following are specifications for the 1738 ArmorPOINT Encoder/Counter
module.
ArmorPOINTArmorPOINT 1738-IJM23 Module
Input Specifications
Number of Inputs 1 – 1 group of A/A return, B/B return, and Z/Z return
Input Voltage 5V
Input Current 19.1 mA @ 5V DC
25.7 mA @ 6V DC
Input OFF-State Voltage <1.25V DC
Input OFF-State Current, max <0.250 mA
Input ON-State Voltage >2.6V DC
Input ON-State Current >5 mA
Maximum ON-State Voltage +6V
Input Filter Selections
(per A/B/Z group)
Off
10 μs
100 μs
1.0 ms
10.0 ms
Maximum Input Frequency 1.0 MHz counter and encoder X1 configurations
500 kHz encoder X2 configuration (no filter)
250 kHz encoder X4 configuration (no filter)
Keyswitch Position 2
General Specifications
LED Indicators 1 yellow input status, logic side
1 green/red network status, logic side
1 green/red module status, logic side
POINTBus Current, max 160 mA
Power Dissipation, max 1.1 W @ rated load
Thermal Dissipation, max 3.75 BTU/hr @ rated load
Isolation Voltage
(continuous-voltage withstand rating)
50V rms
Tested @ 1250V AC rms for 60s
External DC Power (does not represent power
required to supply outputs)
No additional external power required to power module
Dimensions
(H x W x D)
31.75 x 66.80 x 107.95 mm
(1.25 x 2.63 x 4.25 in.)
Temperature, Operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60°C (-4...140°F)
Temperature, Nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
-40...85°C (-40...185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Nonoperating Damp Heat):
5...95% noncondensing
Shock, Operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
30g
Shock, Nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50g