Publication 1738-IN008A-EN-E - June 2004
ArmorPoint Relay Output Modules, Series A 7
Wire the Relay
Output Modules
Following are wiring instructions for the ArmorPoint relay output
modules.
1738-OW4M12
1738-OW4M12AC
ATTENTION
Make sure all connectors and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.
(view into connector)
Pin 1 - 24V dc
Pin 2 - Output 0B (M12-A)
Output 1B (M12-B)
Output 2B (M12-C)
Output 3B (M12-D)
Pin 3 - Common
Pin 4 - Output 0A (M12-A)
Output 1A (M12-B)
Output 2A (M12-C)
Output 3A (M12-D)
Pin 5 - No Connect
43664
(view into connector)
Pin 1 - L1
Pin 2 - L2/N
Pin 3 - Output 0A (M12-A)
Output 1A (M12-B)
Output 2A (M12-C)
Output 3A (M12-D)
Pin 4 - Output 0B (M12-A)
Output 1B (M12-B)
Output 2B (M12-C)
Output 3B (M12-D)
43767