16 SLC 500™ RTD/Resistance Input Module
Publication 1746-IN012B-EN-P - May 2001
Channel Configuration
Once the module is installed, each channel can be configured to establish the way
the channel will operate. You configure the channel by entering bit values into the
configuration word using your programming software. Channels 0 through 3 on the
NR4 are configured by entering bit values into output words 0 through 3
respectively. Output words 4 through 7 are used to further define the channel
configuration to allow you to choose a scaling format other than the module default
when using the proportional counts format. You can use words 4 and 5 to define
one user-set range. Use words 6 and 7 to define a second range. See the table
below for a bit-by-bit examination of the configuration word.
To Select
Make these bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Input Type
100Ω Pt 385 0000
200
Ω Pt 385 0001
500
Ω Pt 385 0010
1000
Ω Pt 385 0011
100
Ω Pt 3916 0100
200
Ω Pt 3916 0101
500
Ω Pt 3916 0110
1000
Ω Pt 3916 0111
10
Ω Cu 426
(1)
1000
120
Ω Ni 618
(2)
1001
120
Ω Ni 672 1010
604
Ω NiFe 518 1011
150
Ω 1100
500
Ω 1101
1000
Ω 1110
3000
Ω 1111
Data Format
Engineering Units 1
(3)
00
Engineering Units
10
(4)
01
Scaled-for-PID 10
Raw/Proportional 11
Broken Input
Set to Zero 00
Set to Upscale 01
Set to Downscale 10
Invalid 1 1
Temperature
Units
(5)
°C 0
°F 1