16 SLC 500™ RTD/Resistance Input Module
Publication 1746-IN012B-EN-P - May 2001
Channel Configuration
Once the module is installed, each channel can be configured to establish the way
the channel will operate. You configure the channel by entering bit values into the
configuration word using your programming software. Channels 0 through 3 on the
NR4 are configured by entering bit values into output words 0 through 3
respectively. Output words 4 through 7 are used to further define the channel
configuration to allow you to choose a scaling format other than the module default
when using the proportional counts format. You can use words 4 and 5 to define
one user-set range. Use words 6 and 7 to define a second range. See the table
below for a bit-by-bit examination of the configuration word.
To Select
Make these bit settings
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Input Type
100 Pt 385 0000
200
Pt 385 0001
500
Pt 385 0010
1000
Pt 385 0011
100
Pt 3916 0100
200
Pt 3916 0101
500
Pt 3916 0110
1000
Pt 3916 0111
10
Cu 426
(1)
1000
120
Ni 618
(2)
1001
120
Ni 672 1010
604
NiFe 518 1011
150
1100
500
1101
1000
1110
3000
1111
Data Format
Engineering Units 1
(3)
00
Engineering Units
10
(4)
01
Scaled-for-PID 10
Raw/Proportional 11
Broken Input
Set to Zero 00
Set to Upscale 01
Set to Downscale 10
Invalid 1 1
Temperature
Units
(5)
°C 0
°F 1