Rockwell-automation 1746-NR8 SLC 500 RTD/Resistance Input Module/ Inst Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
18 SLC 500 RTD/Resistance Input Module
Publication 1746-IN007C-EN-P - December 2002
Input Specifications
RTD Types platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page 21.)
Temperature
Scale (Selectable)
°C or °F and 0.1°C or 0.1°F
Resistance Scale
(Selectable)
1 or 0.1 for all resistance ranges except for 150Ω; or 0.1 or 0.01 for 150
potentiometer.
Input Step
Response
Refer to the SLC 500™ RTD/Resistance Input Module User Manual, publication number
1747-UM003A.
Channel Turn-On
Time
Requires up to one module update time plus module calibration time.
Channel Turn-Off
Time
Requires up to one module update time.
Reconfiguration
Time
Requires up to one module update time plus module calibration time.
Channel Scan
Time (with lead
resistance)
28 Hz = 250 ms
50/60 Hz = 147 ms
800 Hz = 18 ms
6400 Hz = 10 ms
Channel Scan
Time (without lead
resistance)
28 Hz = 125 ms
50/60 Hz = 75 ms
800 Hz = 10 ms
6400 Hz = 6 ms
RTD Excitation
Current
RTD setting:
0.25 mA - Recommended for use with higher resistance ranges for both RTDs and direct
resistance inputs (1000 RTDs and 3000 resistance input). Refer to RTD manufacturer for
recommendations.
1.0 mA -Recommended to use for all other RTD and direct resistance inputs, except 1000
RTDs and 3000 resistance input ranges are limited. Refer to RTD manufacturer for
recommendations.
Vista de pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 24

Comentarios a estos manuales

Sin comentarios