ControlLogix-XT ControlNet Interface Module 9
Publication
1756-IN634A-EN-P - April 2009
Using the 1756-CN2RXT for Standalone or Redundant Control
You can use the 1756-CN2RXT modules either in standalone or
redundant configurations.
A standalone configuration uses:
one control chassis that contains the 1756-CN2RXT and the
175
6-L63XT controller.
one or both channels of the 1756-CN2RXT module connected
to the ControlNet network.
A redundant configuration uses:
two controller chassis called the redundant chassis pair. Each
cha
ssis of the pair must contain at least these modules:
1756-L63XT controller.
1756-CN2RXT ControlNet module.
1756-RMXT redundancy module.
one or both channels of the 1756-CN2RXT module connected
to the ControlNet network.
For more information about redundancy control, refer to the
ControlLogix Redundancy System User Manual, publication
1756-UM523.
IMPORTANT
If you are using the 1756-CN2RXT in a redundant system, these hardware
considerations must be made:
Each redundant chassis of the pair must be configured with identical
modules placed in identical slots. These module pairings between the
two chassis are called partners.
All partner modules in redundant chassis pairs must be at the same
firmware revision.
For ControlNet module partners, the ControlNet network address must
be the same for each module of the pair.
These modules cannot be used in redundant chassis pairs that contain
1756-CN2RXT modules:
1756-DHRIOXT or 1756-DHRIO
1756-SRM