ControlLogix Controller and Memory Board 43
Publication
1756-IN101L-EN-P - June 2008
Conducted RF immunity IEC 61000-4-6:
• 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80
MHz
Enclosure type rating None, open style
Isolation voltage 30V (continuous), Basic Insulation Type, RS232 to system
• Controllers type tested to withstand 707V DC for 60 s
Wiring category
(1)
2 - on communications ports
Programming cable 1756-CP3 or 1747-CP3 serial cable
North American temperature
code
T4A
IEC temperature code T4
Intrinsically safe No
Replacement battery 1756-L1, 1756-L1M1, 1756-L1M2, 1756-L1M3:
1756-BA1 (0.59 g lithium)
1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23, 1756-L55M24:
1756-BA1 (0.59 g lithium)
1756-L61/A, 1756-L62/A, 1756-L63/A:
1756-BA1 (0.59 g lithium)
1756-L61/B, 1756-L62/B, 1756-L63/B, 1756-L64/B, 1756-L65/B:
1756-BA2(0.50 g lithium)
1756-BATM battery module:
1756-BATA (10 g lithium)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
ControlLogix Controller Common Specifications - 1756-L1, 1756-L1M1,
1756-L1M2, 1756-L1M3, 1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23, 1756-L55M24, 1756-L61, 1756-L62,
1756-L63, 1756-L64, and 1756-L65
Attribute Value