Compact™ 1769-IF4 (Series B or Later) Analog Input Module 15
Publication 1769-IN048A-EN-P
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Input Data File
For each input module, slot x, words 0-3 in the input data file contain the
analog values of the inputs.
The bits are defined as follows:
SGN = Sign bit in two’s complement format
Sx = General status bit for channels 0 through 3. This bit is set (1) when
an error (over- or under-range) exists for that channel.
Ux = Under-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
Ox = Over-range flag bits for channels 0 through 3. These bits can be
used in the control program for error detection.
Wire Type Wire Size Terminal Screw
Torque
Retaining Screw
Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Word
Bit Position
15 14131211109876543210
0 SGN Analog Input Data Channel 0
1 SGN Analog Input Data Channel 1
2 SGN Analog Input Data Channel 2
3 SGN Analog Input Data Channel 3
4 Not Used S3 S2 S1 S0
5 U0 O0U101U2O2U3O3 Set to 0