Installation Instructions
CompactLogix Isolated Analog
Input Module
Catalog Number
1769-IF4I
Topic Page
Important User Information 2
North American Hazardous Location Approval 3
Module Description 5
Prevent Electrostatic Discharge 6
System Assembly 6
Mounting Expansion I/O 7
Replacing a Single Module within a System 9
Replacement Part 10
System Wiring Guidelines 10
I/O Memory Mapping 14
Specifications 18
Additional Resources 23
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - Input Module

Installation InstructionsCompactLogix Isolated Analog Input ModuleCatalog Number 1769-IF4ITopic PageImportant User Information 2North American Hazardo

Pagina 2 - Important User Information

10 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 20117. Slide the replacement module into the open slot.8. Connect

Pagina 3 - Risque d’Explosion –

CompactLogix Isolated Analog Input Module 11Publication 1769-IN074C-EN-P - March 2011• Voltages on Ch+, Ch-, and Ch_iRtn for a single, isolated ch

Pagina 4 - Environment and Enclosure

12 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Wiring Single-ended Sensor/Transmitter TypesWiring Mixed Tran

Pagina 5 - Module Description

CompactLogix Isolated Analog Input Module 13Publication 1769-IN074C-EN-P - March 2011Labeling the TerminalsA removable, write-on label is provided

Pagina 6 - System Assembly

14 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011You can use the bare wire or a spade lug. The terminals will

Pagina 7 - Mounting Expansion I/O

CompactLogix Isolated Analog Input Module 15Publication 1769-IN074C-EN-P - March 2011The bits are defined as follows:• SGN = Sign bit in two’s com

Pagina 8 - Panel Mounting

16 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Configuration Data FileThe manipulation of the bits from this

Pagina 9 - DIN Rail Mounting

CompactLogix Isolated Analog Input Module 17Publication 1769-IN074C-EN-P - March 2011The bits are defined as follows:• EC = Enable Channel• Inpt D

Pagina 10 - System Wiring Guidelines

18 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011SpecificationsBit Definitions for Input Range and Input Data

Pagina 11 - Analog Source

CompactLogix Isolated Analog Input Module 19Publication 1769-IN074C-EN-P - March 2011Temperature, operating• IEC 60068-2-1 (Test Ad, Operating Col

Pagina 12

2 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Important User InformationSolid-state equipment has operationa

Pagina 13 - Labeling the Terminals

20 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Surge transient immunityIEC 61000-4-5±1 kV line-earth(CM) on

Pagina 14 - I/O Memory Mapping

CompactLogix Isolated Analog Input Module 21Publication 1769-IN074C-EN-P - March 2011Input SpecificationsAttribute 1769-IF4IAnalog normal operatin

Pagina 15 - Output Data File

22 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Input Specifications (cont.)Attribute ValueAccuracy drift wit

Pagina 16 - Configuration Data Array

CompactLogix Isolated Analog Input Module 23Publication 1769-IN074C-EN-P - March 2011Additional ResourcesThese documents contain additional inform

Pagina 17 - 15 14131211109876543210

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400Publication 1769-IN074C-EN-P - Mar

Pagina 18 - Specifications

CompactLogix Isolated Analog Input Module 3Publication 1769-IN074C-EN-P - March 2011North American Hazardous Location ApprovalThe following inform

Pagina 19 - Attribute 1769-IF4I

4 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Environment and EnclosureATTENTION: This equipment is intended

Pagina 20

CompactLogix Isolated Analog Input Module 5Publication 1769-IN074C-EN-P - March 2011Module DescriptionItem Description Item Description1Bus lever

Pagina 21 - Input Specifications

6 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Prevent Electrostatic DischargeRemove PowerSystem AssemblyThe

Pagina 22 - Input Specifications (cont.)

CompactLogix Isolated Analog Input Module 7Publication 1769-IN074C-EN-P - March 20111. Disconnect power.2. Check that the bus lever of the module

Pagina 23 - Certifications 1769-IF4I

8 CompactLogix Isolated Analog Input ModulePublication 1769-IN074C-EN-P - March 2011Grounding the ModuleMinimum SpacingMaintain spacing from enclo

Pagina 24 - Automation, Inc

CompactLogix Isolated Analog Input Module 9Publication 1769-IN074C-EN-P - March 20114. Drill and tap the mounting holes for the recommended M4 or