Compact™ 16-Point 100 to 240V ac Solid State Output Module 13
Publication 1769-IN061A-EN-P - December 2001
Fault Value Word
The fault value word, word 4, is used to program
the fault state value (0=Off, 1=On). Each output
is individually configurable for on or off.
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data
value, the program or fault value, to apply to the
output if a system in Program mode undergoes a
system fault, resulting in a change to the Fault
mode.
Module Default Condition
The modules default condition is all zeros, programming the conditions shown
below.
Spare/Replacement Module Parts
• Terminal Block:1769-RTBN18 (1 per kit)
Word or Bit Affected Condition Applied
Word 0, Bit 0: Program-to-Fault Enable Program Value
Word 1: Program State User-defined Safe State
Word 2: Program Value Off
Word 3: Fault State User-defined Safe State
Word 4: Fault Value Off
Value Bit Setting
Off 0
On 1
Value Applied Bit Setting
Program 0
Fault 1