18 Compact 1769-OF8C Analog Output Module
Publication 1769-IN065C-EN-P - June 2010
Local:1:C.Ch1En BOOL Decimal
+ Local:1:C.Ch1Range SINT Decimal
+ Local:1:C.Ch1DataFormat SINT Decimal
+ Local:1:C.Ch1FaultValue INT Decimal
+ Local:1:C.Ch1ProgValue INT Decimal
+ Local:1:C.Ch1LClampValue INT Decimal
+ Local:1:C.Ch1HClampValue INT Decimal
+ Local:1:C.Ch1RampRate INT Decimal
Tag Name To Select
Make These Bit Settings
(1)
15-876543210
Ch#ProgToFaultEn Enable 1
Disable 0
Ch#HoldForInit Enable 1
Disable 0
Ch#ProgMode Enable 1
Disable 0
Ch#FaultMode Enable 1
Disable 0
Ch#RampEn Enable 1
Disable 0
Ch#AlarmLatchEn Enable 1
Disable 0
Ch#OverRangeInterruptEn Enable 1
Disable 0
Ch#UnderRangeInterruptEn Enable 1
Disable 0
Ch#En Enable 1
Disable 0
Ch#Range 0…20 mA dc 0
4…20 mA dc 1
Ch#DataFormat Raw/proportional
counts
00
Engineering units 0 1
Scaled for PID 1 0
Percent range 1 1
(1)
All bit positions left blank in table must be set to 0.