12 Compact 1769-OF8V Analog Output Module
Publication 1769-IN066D-EN-P - June 2010
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
I/O Memory Mapping
Output Data File
For each module, slot x, words 0-7 in the output data file contain the channel 0 through
channel 7 output data. Word 8 is used to unlatch any alarm condition that has been latched.
Refer to the Compact™ Analog I/O User Manual, publication number 1769-UM002 for
additional details.
• SGN = Sign bit in two’s complement format.
• UU = Unlatch under-range (or low-clamp exceeded) alarm.
• UO = Unlatch over-range (or high-clamp exceeded) alarm.
Wire Type Wire Size Terminal Screw
Torque
Retaining Screw
Torque
Solid Cu-90°C (194°F) #14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Stranded Cu-90°C (194°F) #16 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
If you are using RSLogix 5000, version 15, please refer to RSLogix 5000,
Version 15, Controller Tags on page 17.
Word
Bit Position
1514131211109876543210
0 SGN Analog Output Data Channel 0
1 SGN Analog Output Data Channel 1
2 SGN Analog Output Data Channel 2
3 SGN Analog Output Data Channel 3
4 SGN Analog Output Data Channel 4
5 SGN Analog Output Data Channel 5
6 SGN Analog Output Data Channel 6
7 SGN Analog Output Data Channel 7
8 UU7 UO7 UU6 UO6 UU5 UO5 UU4 UO4 UU3 UO3 UU2 UO2 UU1 UO1 UU0 UO0