AC (120V) Input Module 9
Publication 1771-IN032B-EN-P - July 2002
Table A
Module Input Terminal Assignments
Terminal
Number
Input Assignment I/O program address Terminal
Number
Input Assignment I/O program address
01 Input 00 1RG00 21 Input 00 1RG00
02 Input 01 1RG01 22 Input 01 1RG01
03 Input 02 1RG02 23 Input 02 1RG02
04 Input 03 1RG03 24 Input 03 1RG03
05 Input 04 1RG04 25 Input 04 1RG04
06 Input 05 1RG05 26 Input 05 1RG05
07 Input 06 1RG06 27 Input 06 1RG06
08 Input 07 1RG07 28 Input 07 1RG07
09 Common 0 (L2)
1
- 29 Common 3 (L2)
1
-
10 Common 0 (L2)
1
- 30 Common 3 (L2)
1
-
11 Input 10 1RG10 31 Not used 1RG10
12 Input 11 1RG11 32 Input 11 1RG11
13 Input 12 1RG12 33 Input 12 1RG12
14 Input 13 1RG13 34 Input 13 1RG13
15 Input 14 1RG14 35 Input 14 1RG14
16 Input 15 1RG15 36 Input 15 1RG15
17 Input 16 1RG16 37 Input 16 1RG16
18 Input 17 1RG17 38 Input 17 1RG17
19 Common 1 (L2)
1
- 39 Common 4 (L2)
1
-
20 Common 1 (L2)
1
- 40 Common 4 (L2)
1
-
Where: R = rack number (1, 2, 3, etc.)
G = I/O group (0 - 7)
1
You can connect a different power supply to each common (0,1,2 and 3). Terminals 09/10 are common for terminals 01 thru 08;
19/20 for 11 thru 18; 29/30 for 21 thru 28; 39/40 for 31 thru 38. If multiple power supplies are used, do not exceed the specified
isolation voltage.