Interpreting Diagnostic Information
In LEDs and Error Codes
Chapter 5
5-9
8000 Series Communication-network Error Codes
The SPI module returns these protocol-related error codes (Table 5.E) in the
CDS when it detects network-related errors.
Table 5.E
Communicationnetwork
Error Codes
Error Code Type of Error The SPI module detected:
8000 no response, timedout that the device did not respond to the command within the 1 sec time limit
8001 no status, timedout that the device accepted the command but did not return status within the
0.1 sec time limit
8002 numeric overrange a numeric command value in CDB exceeded 32,767 decimal
8003 buffer overrun the command was too large and overran the buffer
8004 communication an unspecified communication error on the SPI link
8005 checksum a checksum error in status received from a device
8006 device termination early termination of status received from the device
8007 device address an AF hex character, but the format (MCC word 1, bit 8) specified decimal
8008 numeric overrange a numeric status value from a device exceeded 32767 decimal
8009 illegal address/ID the device/ID address of the CDB did not match any of the
device/ID addresses stored in the SPI module's configuration
800A numeric word an AF hex character, but the format (MCC word 1, bit 8) specified decimal
800B
illegal ID
the ID of a CDB is not currently stored in custom configuration
800C the ID of a CDB is not a SPIspecified ID
800D link timeout there has been no communication on the link within the 1.2 sec time limit