Publication 1785-IN019B-EN-P - January 2007
Installation Instructions
PLC-5 Ethernet Interface Module
Catalog Number 1785-ENET,
Series C, Revision B
About This Publication
This publication helps you:
understand what equipment you need to install
the module.
install and configure the module.
connect to an Ethernet link and communicate
via the module.
Topic Page
About This Publication 1
Important User Information 2
About the Module 5
Before You Begin 15
Install the Module 16
Establish an Ethernet Connection 26
Monitor Ethernet Status Data 27
Use the Message Instruction 27
Interpret Error Codes 30
Domain Name Service 31
Embedded Web Server 32
Interpret the LED Indicators 43
Specifications 45
Additional Resources 47
Vista de pagina 0
1 2 3 4 5 6 ... 47 48

Indice de contenidos

Pagina 1 - Series C, Revision B

Publication 1785-IN019B-EN-P - January 2007Installation InstructionsPLC-5 Ethernet Interface ModuleCatalog Number 1785-ENET, Series C, Revision BAbout

Pagina 2 - Important User Information

10 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007If you want to send an email to a specific recipient when a controlle

Pagina 3 - Environment and Enclosure

PLC-5 Ethernet Interface Module 11Publication 1785-IN019B-EN-P - January 2007Channel 3A StatusFollow these directions to check the status of chann

Pagina 4 - AVERTISSEMENT

12 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Enable/Disable HTTP Web ServerYou can disable the HTTP Web server fun

Pagina 5 - About the Module

PLC-5 Ethernet Interface Module 13Publication 1785-IN019B-EN-P - January 2007Web Diagnostics and Module InformationThis enhancement is a user-frie

Pagina 6 - Channel 3A Default

14 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007The additional diagnostics are available for use within a user progra

Pagina 7

PLC-5 Ethernet Interface Module 15Publication 1785-IN019B-EN-P - January 2007Before You BeginFollow these directions before installing your module

Pagina 8 - Set Negotiation Order

16 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Parts ListRequired ToolsThe 1785-ENET is a modular component of the 1

Pagina 9 - Enter the SMTP IP Address

PLC-5 Ethernet Interface Module 17Publication 1785-IN019B-EN-P - January 20073. Install the combination into the chassis.Attach the Connector Head

Pagina 10

18 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Connect the Module to the Controller1. Align the pins and holes on th

Pagina 11 - Channel 3A Status

PLC-5 Ethernet Interface Module 19Publication 1785-IN019B-EN-P - January 2007Install the Module Combination into the ChassisWith grounding wrist s

Pagina 12 - Domain Name Service (DNS)

2 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Important User InformationSolid state equipment has operational charac

Pagina 13

20 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 20074. Lower the locking bar into place.Configure the Module for Ethernet

Pagina 14 - 44 Not used

PLC-5 Ethernet Interface Module 21Publication 1785-IN019B-EN-P - January 2007Use your programming software package to designate channel 3A as the

Pagina 15 - Before You Begin

22 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Enter configuration information in the appropriate fields.This Field

Pagina 16 - Install the Module

PLC-5 Ethernet Interface Module 23Publication 1785-IN019B-EN-P - January 2007After entering the channel 3A configuration information, either accep

Pagina 17

24 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007With all hardware and IP addresses in one location, you can easily ch

Pagina 18

PLC-5 Ethernet Interface Module 25Publication 1785-IN019B-EN-P - January 2007EXAMPLEThe following system shows three controllers (two enhanced con

Pagina 19

26 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Based on this configuration, the BOOTPTAB file would look like this:R

Pagina 20 - Configure Channel 3A

PLC-5 Ethernet Interface Module 27Publication 1785-IN019B-EN-P - January 2007Monitor Ethernet Status DataMonitor communication status through the

Pagina 21 - Specify Ethernet Information

28 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007The MSG instruction transfers data in packets. Each packet can contai

Pagina 22

PLC-5 Ethernet Interface Module 29Publication 1785-IN019B-EN-P - January 2007The IP address specifies the MSG instruction’s destination node. If t

Pagina 23

PLC-5 Ethernet Interface Module 3Publication 1785-IN019B-EN-P - January 2007Environment and EnclosurePrevent Electrostatic DischargeATTENTIONThis

Pagina 24

30 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Interpret Error CodesWhen the controller/interface module detects an

Pagina 25

PLC-5 Ethernet Interface Module 31Publication 1785-IN019B-EN-P - January 2007Identify the Module Within a NetworkThe PLC-5 Ethernet Interface Modu

Pagina 26 - Apply Power to the Chassis

32 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007With the latest release of the Ethernet PLC-5 controllers and RSLogix

Pagina 27 - Use the Message Instruction

PLC-5 Ethernet Interface Module 33Publication 1785-IN019B-EN-P - January 2007This page displays general messaging statistics. Use the information

Pagina 28 - Parameter Descriptions

34 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007The second list contains Application Level Statistics. These pages pr

Pagina 29

PLC-5 Ethernet Interface Module 35Publication 1785-IN019B-EN-P - January 2007To change the refresh data function back to the default of 15 seconds

Pagina 30 - Interpret Error Codes

36 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007• %format - legal values are %d for decimal and %x for hexadecimal. T

Pagina 31 - Domain Name Service

PLC-5 Ethernet Interface Module 37Publication 1785-IN019B-EN-P - January 2007Generate Custom Data Table Monitor PagesYou can generate Custom Data

Pagina 32 - Embedded Web Server

38 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007All other file types are displayed in an appropriate format. If a % f

Pagina 33

PLC-5 Ethernet Interface Module 39Publication 1785-IN019B-EN-P - January 200713. Click +A22.You can change the radix display of N7:0 through N7:2.

Pagina 34

4 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007North American Hazardous Location ApprovalThe following information ap

Pagina 35 - Reference Data Table Memory

40 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Interfaces ifIndex Interface numberifDescr Description of the interfa

Pagina 36 - HTML Examples

PLC-5 Ethernet Interface Module 41Publication 1785-IN019B-EN-P - January 2007IP ipForwarding Acting as a gateway or hostipDefaultTTL Default TTL f

Pagina 37

42 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007IP ipRouteProto Mechanism used to determine routeipRouteAge Age of ro

Pagina 38

PLC-5 Ethernet Interface Module 43Publication 1785-IN019B-EN-P - January 2007Interpret the LED IndicatorsIf your module is operating correctly, yo

Pagina 39 - SNMP MIB II Data Groups

44 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Monitor the series of blinks to determine the fault code. Count the f

Pagina 40

PLC-5 Ethernet Interface Module 45Publication 1785-IN019B-EN-P - January 2007Controller Fault CodesSpecificationsFault Code Description91 Module u

Pagina 41

46 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007Environmental SpecificationsAttribute ValueOperating Temperature

Pagina 42

PLC-5 Ethernet Interface Module 47Publication 1785-IN019B-EN-P - January 2007CertificationsAdditional ResourcesYou can view or download publicatio

Pagina 43 - Interpret the LED Indicators

Publication 1785-IN019B-EN-P - January 2007 PN 953014-07Supersedes Publication 1785-IN019A-EN-P - August 2005 Copyright © 2007 Rockwell Automation, In

Pagina 44 - Module Error Codes

PLC-5 Ethernet Interface Module 5Publication 1785-IN019B-EN-P - January 2007European Hazardous Location ApprovalAbout the ModuleThe PLC-5 Ethernet

Pagina 45 - Specifications

6 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007PLC-5 Series/Revision CompatibilityAll ControlNet 1.5 PLC-5 controller

Pagina 46 - Environmental Specifications

PLC-5 Ethernet Interface Module 7Publication 1785-IN019B-EN-P - January 2007Follow these directions to see or activate the new configuration and s

Pagina 47 - Additional Resources

8 PLC-5 Ethernet Interface ModulePublication 1785-IN019B-EN-P - January 2007When you create a hostname, consider these naming conventions.• The ho

Pagina 48 - Rockwell Automation Support

PLC-5 Ethernet Interface Module 9Publication 1785-IN019B-EN-P - January 2007Unchecked Autonegotiate Checkbox and Corresponding Port SettingsChecke