For A-B Internal Use Only Publication 1785-6.2 March 1998
3. Select the appropriate script file by moving the cursor to the file name and
pressing . Script files are named as follows:
Lwwx_yz.ini
4. On your computer, select the communication port (COM1 or COM2) by
moving the cursor to select the port and pressing .
5. Make sure you have established a connection. This could take about
60 seconds.
Where: Represents:
ww
11, 20, 26, 30, 40, 46, 60, 80, or 86
depending on what flash upgrade you are
trying to download to the processor.
x
the type of flash upgrade to download:
B (for Enhanced)
L (for Extended-local I/O)
C (for ControlNet 1.0 or 1.25)
E (for Ethernet)
C15 (for ControlNet 1.5)
y
the series of the flash upgrade to download
(see the disk label)
z
the revision of the flash upgrade to download
(see the disk label)
If you: The screen displays:
established a connection information about the target processor
The processor’s PROC LED flashes
red/green.
did not establish a connection an error message
See the following table.
Return
Return