Rockwell-automation 1790-XXXX CompactBlock LDX I/O DeviceNet RTD and T Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
11
Publication 1790-IN011B-EN-P - April 2003
To ensure that the lead values match as closely as
possible:
keep lead resistance as small as possible and less than
25 ohms
use quality cable that has a small tolerance impedance
rating
use a heavy-gauge lead wire which has less resistance
per foot
RTD Wiring Configurations
Three configurations of RTDs can be connected to the
blocks:
2-wire RTD, which is composed of an RTD EXC
(excitation) lead wire and a RTN (return) wire
3-wire RTD, which is composed of a Sense and 2 RTD
lead wires (RTD EXC and RTN)
4-wire RTD, which is composed of a Sense and 2 RTD
lead wires (RTD EXC and RTN). The second sense
wire of a 4-wire RTD is left open.
2-Wire RTD Configuration
CH0_A
CH0_B
COM
Add Jumper
Cable Shield (to Ground)
RTD EXC RTD EXC
Return Return
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 23 24

Comentarios a estos manuales

Sin comentarios