ArmorBlock 4 Output Module28
Publication 1792-5.4 – October 1996
Reset Faults using Explicit Message Program Control
You can also reset outputs using the Explicit Message Program Control
feature on the Scanner module master. Refer to the specific scanner
publications for information on using this feature.
The format for the reset explicit message transaction block must
contain 6 words as shown below:
Word Input Fault
Transaction
Header
W
ord 0
TXID – CMD/ST
ATUS
W
ord 1
PORT – SIZE
W
ord 2
Service = 32 hex – MAC ID
T
ransaction Body
W
ord 3
Class = 9
W
ord 4
Instance = n – where n = number of the output (1 through
4)
W
ord 5
Attribute = 0
Attribute Data = 0