10 ArmorBlock MaXum 12 Input/ 4 Output Module With Ground Lug
Publication
1792D-IN056A-EN-P - October 2004
Communicate With Your ArmorBlock MaXum I/O Module
This ArmorBlock module’s I/O is exchanged with the master through
a cyclic, poll, or change-of-state connection.
The module consumes and produces I/O data as follows:
Cyclic - allows configuration of the block as an I/O client. The block
will produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O
message to the module. The 12 input / 4 output module consumes
the message, updates outputs, and produces a response. The
response has input data, input faults, output faults, and the status of
the auxiliary power.
Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the
I/O module is alive and ready to communicate. Consumption occurs
when data changes and the master produces new output data to the
I/O block.
Refer to the table below for the word/bit definitions.
Type of I/O Connections Consumes Produces
Cyclic 1 Byte 4 Bytes
Polled 1 Byte 4 Bytes
Change-of-State 1 Byte 4 Bytes
Bit 07 06 05 04 03 02 01 00
Produces 0 I7 I6 I5 I4 I3 I2 I1 I0
Produces 1 ISC-D ISC-C ISC-B ISC-A I11 I10 I9 I8
Produces 2 OW-F OW-E OW-D OW-C OW-B OW-A ISC-F ISC-E
Produces 3 RSVD OPWR RSVD RSVD OFLT3 OFLT2 OFLT1 OFLT0
Consumes 0 RSVD RSVD RSVD RSVD O3 O2 O1 O0
Where: I = Input, ISC = Input Short Circuit in Sensor Source Voltage, OW = Off Wire,
RSVD = Reserved, OPWR = Output Power (auxiliary power), OFLT = Output fault, O = Output