ArmorBlock LP2 2 Sinking Input Module 9
Publication 1792D-5.43 - July 1999
Specifications
4 Input Module - Cat. No. 1792D-2BOLP
Sinking Input Specifications Max Min
Inputs per block 2- 3 wire or dry contact PNP devices
Sensor Source Current (per input) 100mA -
On-state Voltage 25V dc 10V dc
On-state Current 10mA 2mA
Off-state Voltage 5V dc -
Off-state Current - 1.5mA
General Specifications
Indicators Network Status - red/green
Module Status - red/green
Point LED - yellow
Communication Rate • 125Kbps @ 500 meters (1600 feet) for thick
cable, flat media length 375 meters (1230 feet)
• 250Kbps @ 200 meters (600 feet) for thick
cable, flat media length 150 meters (492 feet)
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters (246 feet)
DeviceNet Power: Voltage
Current
25V dc max
125mA (no sensors)
300mA (full load)
11V dc min
Dimensions (assembled to base)
inches - (millimeters)
1.023H x 2.7W x 4.72D
(26)H x (68.5)W x (120)D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-25 to 60
o
C (-13 to 140
°
F)
-25 to 80
o
C (-13 to 176
°
F)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11 (+1) ms pulse width
Tested 10g @ 10-500 Hz per IEC 68-2-6
Conductors Publication DN-6.7.2
Enclosure Meets or exceeds IP67
Agency Certification
(when product is marked)
• CE marked for all applicable directives
Product Data (user information) Publication 1792-2.1
Comentarios a estos manuales