6 FLEX Integra 4 Input Module
Publication 1793-5.1 - September 1999
Memory Mapping
Setting the Input Delay Time
You can select the input delay time (DT) for channels 00 thru 03. Select the
input delay time by setting the corresponding bits in the output image table
(complementary word) for the module.
For example, to set a delay time of 4ms for an input module at address rack
1, module group 0, set bits 02, 01 and 00 as shown below.
Input Delay Times
Bit/
Word
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Read Reserved I3 I2 I1 I0
Write Reserved DT 00-03
Where: I = Input
DT = delay time - refer to “Setting the Input Delay Time”
02 01 00 Filter Time for Inputs 00-03
Selected
Filter Time
000Filter Time 0 (default) 512
μ
s
001Filter Time 1 1ms
010Filter Time 2 2ms
011Filter Time 3 4ms
100Filter Time 4 8ms
101Filter Time 5 16ms
110Filter Time 6 32ms
111Filter Time 7 64ms
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
011
= 3 Octal or 3 decimal
Write delay time on system startup.
Write DT to complement
of input module.
Fill File
Source
Destination
Length
3
#O:010
1
I:000
00
FLL
O:010
Dec.
41335