Rockwell-automation 1793-OV16 Flex Integra Output Module Install Inst Manual de usuario Pagina 8

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 8
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 7
Publication 1793-5.11 - December 1999 PN957259-18
Supersedes publication 1793-5.11 - September 1999 © (1999) Rockwell International Corporation.Printed in USA
Output Signal Delay Time
Off to On
On to Off
0.5ms maximum
1.0ms maximum
Flexbus Current 80mA maximum
Power Dissipation 4.2W @ 31.2V dc
Thermal Dissipation 14.3 BTU/hr @ 31.2V dc
Indicators 16 yellow channel status indicators
Fusing Outputs are electronically protected
External dc Power Voltage
Current
19.2-31.2V dc (5% ac ripple)
49mA
Dimensions Inches
(Millimeters)
2.72H x 3.7D x 3.2W
(69H x 94D x 80W)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Nonoperating
Vibration
0 to +55
o
C (32 to +131
o
F)
-40 to +85
o
C (-40 to +185
o
F)
5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+
1)ms pulse width
Tested to 50g peak acceleration, 11(+
1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
Conductors Wire Size
Category
12 gauge to 18 gauge (4mm
2
to 0.75mm
2
)
stranded wire rated @ 75
o
C minimum
3/64 in (1.2mm) maximum insulation
2
1
Screw Terminal Torque 5-7 lb-in (0.5-0.6Nm)
Agency Certification
(when product is marked)
C-UL Listed
C-UL Class I, Division 2 Groups A, B, C and D certified
UL listed
CE marked for all applicable directives
C-Tick marked for all applicable acts
1 Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”
Specifications - 16 Protected Output Module Cat. No. 1793-OV16P and -OV16PS
Vista de pagina 7
1 2 3 4 5 6 7 8

Comentarios a estos manuales

Sin comentarios