FLEX I/O™ Dual Port EtherNet/IP Adapter Modules 5
Publication 1794-IN131A-EN-P - January 2012
General Specifications
Indicator Status
Link 1 or Link 2 (individually)
Off No link exists. Verify network cabling. Correct as necessary.
Solid green Link exists at 100 Mbps.
Flashing green I/O is being transmitted or received at 100 Mbps.
Flashing yellow I/O is being transmitted or received at 10 Mbps.
Solid yellow Link exists at 10 Mbps.
Module Status Indicator
Off No power. Adapter does not have 24V DC power. Make sure
power is being supplied to the adapter.
Flashing green Standby. Adapter not configured. Configure adapter.
Green Operational. Adapter operating correctly. No action
required.
Flashing red Minor fault. A recoverable fault has been detected. This
could be caused by an incorrect or inconsistent
configuration.
Check configuration and reconfigure as needed.
Solid red Major fault. An unrecoverable fault has been detected.
Recycle power to the adapter. If this does not clear the
fault, replace the adapter.
Flashing red/green Self test. Adapter performing power-up self test. Wait until
completed.
Network Status Indicator
Off Not powered. No IP address. Adapter is not powered or
does not have an IP address.
Verify there is power and the adapter is correctly wired to
the power supply.
Make sure the adapter is configured.
Flashing green No connection. Adapter has obtained an IP address, but has
no established connections.
Green CIP connections. Adapter has an IP address and at least one
established connection.
Flashing red Connection timeout. One or more of the connections in
which the adapter is the target has timed out.
Red Duplicate IP address. Adapter has detected that its IP
address is already in use. Configure the adapter with a
unique IP address.
Flashing red/green Self-test. Adapter performing power-up self test.
Attribute Value
I/O capacity 8 modules
Power supply To comply with the CE Low Voltage Directive (LVD), this
equipment must be powered from a source compliant with
the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low
Voltage (PELV).
Input voltage rating,
nom
24V DC
Input voltage range 19.2…31.2V DC (includes 5% AC ripple)
Inrush current 18 A for 2 ms
Communication rate 10/100 Mbps
Indicators Module status – red/green
Network status – red/green
Link 1 – yellow/green
Link 2 – yellow/green
FlexBus output 5.0V DC
640 mA, max
Isolation voltage 50V (continuous), Basic Insulation Type
Tested @ 1000V AC for 60 s, power to FlexBus to EtherNet
Power consumption,
max
500 mA,
400 mA @ 24V DC
Power dissipation, max 7.1 W @ 19.2V DC
Thermal dissipation 24.2 BTU/hr @ 19.2V DC
Ethernet connector RJ45 Cat. 5
Enclosure type rating None (open-style)
Wire size Power conductors:
0.33…3.31 mm
2
(22…12 AWG) stranded copper wire rated
@ 75
°C (167 °F) or greater, 1.2 mm (3/64 in.) insulation
max
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication
1770-4.1.
1 – on power ports
2 – on communication ports
North American temp
code
T5 – 1794-AENTR
T4A – 1794-AENTRXT
IEC temp code T5 – for 1794-AENTR
T4 – for 1794-AENTRXT
Terminal screw torque 0.8 Nm (7 lb-in.)
Weight, approx. 227 g (8.01 oz)
Dimensions, HxWxD,
approx.
87.4 x 94 x 92 mm
(3.44 x 3.7 x 3.6 in.)