4–2 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter
    
During normal operation, the processor transfers from 1 to 4 words
to the module when you program a BTW instruction to the module’s
address.
Read programming moves status and data from the Pulse Counter
module to the processors data table in one I/O scan. The processors
user program initiates the request to transfer data from the Pulse
Counter module to the processor.
The following read and write words and bit/word descriptions
describe the information written to and read from the Pulse Counter
module. The module uses up to 11 words of input data and up to 3
words of output data. Each word is composed of 16 bits.
Pulse Counter Module (1794ĆIP4) Image Table Mapping
Module Image
I/O Image
Input Size
Output Size
  
  
Counter 00 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 0
Code for identification of software version
Control Word 0 - Sets the measure function
Control Word 2 - sets the start of a new measurement
Control Word 1 - Sets the clock frequency and period multiple
Counter 01 - pulse counter for channel 0 or high word of 32Ćbit period measurement
Counter 10 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 1
Counter 11 - pulse counter for channel 1 or high word of 32Ćbit period measurement
Counter 20 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 2
Counter 21 - pulse counter for channel 2 or high word of 32Ćbit period measurement
Counter 30 - 16-bit period measurement or low word of 32Ćbit period measurement for channel 3
Counter 31 - pulse counter for channel 3 or high word of 32Ćbit period measurement
Readback of Control word 2 or
Reserved M0M1M2M3
RD0RD1RD2RD3
Reading Data From Your
Module
Mapping Data for the
Module