Publication 20P-IN065A-EN-P
Step 3: Remove the
Existing In-Rush Resistor
Important:Mark all connections and wires before removal to avoid incorrect
wiring during reassembly.
1. Disconnect the resistor wires from connector XR-6 on the overvoltage
clipping board.
2. Remove the four screws that secure the resistor to the drive frame and
remove the resistor and wires.
XCD
X1UVW1
XUVW
F31 F21 F11
XR-5 XR-4 XR-3 XR-2 XR-1
C5gn C4blu C7gnC7blu
XR-6
Disconnect wires
Remove
screws
Remove
screws