Rockwell Automation Publication 2100-IN092A-EN-P - April 2013 7
Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch
4. If the unit at the top of the section, directly above the Feeder unit, is a
Main Lug Compartment (Bulletin 2191) unit, a Main Disconnect Switch
(Bulletin 2192M) unit, or a Main Circuit Breaker (Bulletin 2193M) unit,
complete these steps:
a. Remove the plastic retaining clip.
b. Secure the top horizontal wireway pan to the right-hand unit support
with a 1/4-20 bolt, lock washer, and nut.
c. Tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.
5. If the unit at the bottom of the section, directly below the Feeder unit, is a
Main Lug Compartment (Bulletin 2191) unit, a Main Disconnect Switch
(Bulletin 2192M) unit, or a Main Circuit Breaker (Bulletin 2193M) unit,
complete these steps:
a. secure the bottom horizontal wireway pan to the right-hand unit
support with a 1/4-20 bolt, lock washer, and nut:
b. Tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.
Top Horizontal
Wireway Pan
Tighten to 55 lb•in
(6 N•m)
Vista de pagina 6