Bulletin 283 Parameters
Table 9 Starter Display and Parameter Settings
Table 10 FLA Setting Ranges and Default Values (with indicated setting precision)
Parameter Name String Path (hex) Min Max Dflt Type Value
SMC Display
101 Phase A Current 002C – 01 – 08 0 32767 — INT xxx.x Amps
102 Phase B Current 002C – 01 – 09 0 32767 — INT xxx.x Amps
103 Phase C Current 002C – 01 – 0A 0 32767 — INT xxx.x Amps
104 Average Current 002C – 01 – 05 0 32767 — INT xxx.x Amps
105 % Therm Utilized 002C – 01 – 07 0 100 — USINT xxx %
SMC Settings
106 FLA Setting 002C – 01 – 03 See Table 10 below Min I INT xxx.x Amps
107 OL Trip Class 002C – 01 – 04 0 3 1 BYTE 1 = 10
108 OL Reset Level 0029 – 01 – 131 0 100 75 BYTE xxx %
109 Start Time 000F - 06D - 01 1 45 10 USINT sec
110 Start Mode 000F - 06E - 01 0 1 0 BOOL
0 = Current Limit
1 = Soft Start
111 Current Limit 000F - 06 - 01 150 600 350 UINT
xxx % FLA
Display multiplier of 10.
SMC is looking for values
between 15 and 60.
112 Initial Torque 000F - 070 - 01 0 90 60 USINT % LRT
113 Soft Stop Time 000F - 071 - 01 0 90 0 USINT sec
114 Kick Start 000F - 072 - 01 0.0 1.5 0.0 USINT sec
115 SCR Temp Reset Mode 000F - 073 - 01 0 1 0 BOOL
0 = Manual
1 = Auto Reset
116 Phase Rotation 000F - 074 - 01 0 1 0 BOOL
0 = Disable
1 = Enable
FLA Current Range (A)
Default Value
Minimum Value Maximum Value
1.1 3.0 1.1
3.0 5.5 3.0
5.3 7.6 5.3
6.3 16.0 6.3