Rockwell-automation 45MLA Controller Installation Instructions Manual de usuario Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
4
Additionally, the CAN and RS485 controller models offer the
flexibility of adjusting these settings through use of specified
commands over the serial interface.
Resetting Default Parameter Settings
All controllers are shipped with default parameter values, that can
be changed through the teach process for the I/O model and
through serial commands for the RS485 and CAN models. The
default parameters can be reset in all models through the
following procedure:
Turn controller power off.
Set switch 8 on DIP switch array S1 to ON.
Turn controller power on.
Set switch eight on DIP switch array S1 to OFF.
Default settings should now be restored.
Functional Description—Analog Model
Figure 3: Analog Model
The analog controller model offers either 4…20 mA or 0…10V
(current or voltage selectable via DIP switch) output proportional
to target height, width, or position. The output is automatically
scaled to the length of the connected arrays, so most applications
do not require additional adjustments. A teach button is available
for applications that require customized scaling of the output.
In 2
PNP
NPN
PNP
NPN
D7 LED - Power
Analog
Extension
PCB
D3 LED Out 1
D4 LED Out 2
D6 LED In 2
D5 LED In 1
D13 LED
D15 LED
D12 LED
D11 LED
D10 LED
RJ45 Connector
Emitter
RJ45 Connector
Receiver
D2 LED
D1 LED
In 1
Pot 2
Pot 1
Teach
Push-
Button
Removable
Spring-Loaded
Connector
Input
Logic
Jumpers
S1
J2
J15
Out 1
Out 2
In 1
In 2
n. c.
Earth.
24 VDC
0 VDC
D16 LED
Pin Listings
The allocation of pins on the main connector, J2, is specified
below.
Table 6: J2 Pin Listings
The allocation of pins on the I/O extension PCB is described
below.
Table 7: J15 Pin Listings
LED Indicators
The following table describes LED status for LEDs D15 and D16
present on the extension PCB.
Table 8: Analog Board LED Descriptions
DIP Switch Settings
DIP switches 1 through 6 on the S1 DIP switch array are
configured for the various applications described below. If no
information is otherwise provided these DIP switches should
remain in the OFF position.
DIP switch 8 is used to reset default configuration.
Pin Signal Description Remarks
10V DC Power
2+24V DC Power
3 Ground Ground
4 Not connected Not connected
5 In 2 Not used
6In 1
Not used DIP switch S1 (3) = 0
Remote teach DIP switch S1 (3) = 1
7 Out 2 Error
0V DC = error
24V DC = no error
8 Out 1 Light array interrupted
0V DC = interrupted
24V DC = not interrupted
Pin Signal Minimum Maximum
1I Out 4 mA 20 mA
20V DC
3 V Out 0V 10V
40V DC
LED Description Status Meaning
D15 Teach Indicator
Off Teach inactive
Flashing Teach active
Orange Last step of teach process
D16 Analog Output Status
Off V_out = OFF (0V)
Flashing
Start up (ignore output), over
current, or error
Green
Brightness proportional to
analog output
Vista de pagina 3
1 2 3 4 5 6 7 8 9 ... 15 16

Comentarios a estos manuales

Sin comentarios