Installation Instructions
Ultrasonic Discrete Sensors
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.
Specifications
General 300 mm Models 800 mm Models
Sensing range [mm (in.)]
30…300
(1.18…11.81)
50…800
(1.96…31.49)
Adjustment range [mm (in.)]
50…300
(1.96…11.81)
70…800
(2.75…31.49)
Blind Zone [mm (in.)] 0…30 (0…1.18) 0…50 (0…0.96)
Standard target [mm (in.)] 100 x 100 (3.93 x 3.93)
Frequency Approx. 390 kHz Approx. 255 kHz
Response delay Approx. 30 ms Approx. 100 ms
Operating temperature [C (F)] -25…70° (-13…158°)
Storage temperature [C (F)] -40…85° (-40…185°)
Electrical
Operating voltage 10…30V DC
Output current 200 mA
Current consumption 20 mA
Protection type Short-circuit, reverse polarity, overload
Voltage drop <3V
Output
Output type Discrete-PNP with N.O./N.C.
Output Rating 200 mA max.
Repeatability <1%
Switching frequency <13 Hz <4 Hz
Hysteresis 1% of the set operating distance
Sensitivity adjustment
Remote teach/optional programming
cable
Environmental
Enclosure type rating IP67
Shock 30 g, 11 ms
Housing material Brass, nickel-plated
Connection Micro-quick disconnect
Certifications
cULus Listed and CE Marked for all
applicable directives
Models to be covered:
873M-D18PO300-D4
873M-D18RPO300-D4
873M-D18PO800-D4
873M-D18RPO800-D4
Discrete Output Mode
Discrete sensors feature normally-open/normally-closed
PNP outputs.
Includes two teachable set points and multiple output
functions.
The upper and lower sensing range can be scaled to a
distance-fixed window.
The sensor is taught using an easy four-step remote teach
process or an optional programming cord.
LED Displays
Operating Mode Red LED Yellow LED Green LED
Teach Mode
Target detected
One flash
Continuous
flash
OffNo target detected
Flashes Off
Target marginal (invalid
teach)
Standard Mode
Target present
Off
On
On
Target not present
Off
Solid-state devices can be susceptible to
radio frequency (RF) interference
depending on the power and the frequency
of the transmitting source. If RF
transmitting equipment is to be used in the
vicinity of the solid-state devices, thorough
testing should be performed to assure that
transmitter operation is restricted to a safe
operating distance from the sensor
equipment and its wiring.
IMPORTANT
ATTENTION
If a hazardous condition can result from
unintended operation of this device, access
to the sensing area should be guarded.
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Ultrasonic Discrete Sensors

Installation InstructionsUltrasonic Discrete SensorsIMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.SpecificationsGeneral 300 mm Models 800 mm Model

Pagina 2 - Dimensions [mm (in.)]

10000229947 Ver 01September 2012Power, Control and Information Solutions HeadquartersAmericas: Rockwell Automation, 1201 South Second Street, Milwauke

Comentarios a estos manuales

Sin comentarios