Demo Unit User Manual (AADvance Controller)
4-26
Document: 553850 Issue 1.2: March 2011
RTC Program: Day of Month
Direction: output from application to controller
Type: word
Values:
1 to 31
Default 0 (zero)
Description:
Specifies the day of the month part of the date to be written to the real-time clock the
next time the RTC control variable RTC Write is asserted TRUE. The value will be
written only if the RTC control variable Day is TRUE.
RTC Program: Hours
Direction: output from application to controller
Type: word
Values:
0 to 23
Default 0 (zero)
Description:
Specifies the time of day (in hours) to be written to the real-time clock the next time
the RTC control variable RTC Write is asserted TRUE. The value will be written
only if the RTC control variable Hours is TRUE.
RTC Program: Minutes
Direction: output from application to controller
Type: word
Values:
0 to 59
Default 0 (zero)
Description:
Specifies the time of day (in minutes) to be written to the real-time clock the next time
the RTC control variable RTC Write is asserted TRUE. The value will be written
only if the RTC control variable Minutes is TRUE.