Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
2-11
CPU A &
CPU B
3 × T9110 Processor Module, T9100 Processor Base Unit,
O/P A
2 × T9451 Digital Output Module, 24V dc, 8 Channel +
9852 Digital Output TA, 24V dc 8 Channel, Dual
Note: All configurations that use dual or triplicate processor modules are suitable for
SIL3 architectures with de-energize to trip outputs. Dual outputs are also required for
SIL3 energize to action outputs.
Planned Certified Configurations
Table 12: Central Modules
Modules
TÜV Certified
Configuration
Conditions
Processor Module
T9110
1oo1D, 1oo2D,
2oo3D
Safety-related and can be used for safety-critical
applications in SIL2 with 1 module fitted and SIL3
applications with 2 or 3 modules fitted.
Note: For High Demand applications you must use
a minimum of two processors.
Table 13: Input Modules
Modules
TÜV Certified
Configuration
Conditions
Digital Inputs
T9401/2, 24V dc,
8/16 Channel,
isolated.
+
T9801/2/3 Digital
Input TA, 16 channel,
Simplex/Dual/TMR
1oo1D, 1oo2D,
2oo3D
Within a specified safety accuracy limit of 1.0V dc.
De-energized to action (normally energized): SIL3
with 1, 2 or 3 modules fitted.
Energize to action (normally de-energized): with 1, 2
or 3 modules fitted
Note: when the integrity level is at 1oo1D then the
faulty module must be replaced to restore the
integrity level back to 1oo2D.
Analogue Inputs
T9431/2, 8/16
Channel, isolated
+
T9831/2/3 Analogue
Input TA, 16
Channel,
Simplex/Dual/TMR
1oo1D, 1oo2D,
2oo3D
Within the manufactures specified safety accuracy
limits of 200µA. The safety state of the analogue
input has to be set to a safe value which is a
calculated value based on a count value of 0mA.
(refer to the AADvance Configuration Guide Doc
no: 553633 for more details)
SIL3 with 1, 2 or 3 modules fitted.
Note: when the integrity level is at 1oo1D then the
faulty module must be replaced within the MTTR
assumed for the PFD calculations to restore the
integrity level back to 1oo2D.