Rockwell-automation AADvance Controller Troubleshooting and Maintenanc Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 96
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
2-6
Document: 553634
(ICSTT-RM406F_EN_P) Issue: 089:
Troubleshooting and Maintenance Manual (AADvance
Controller)
Perform the Manual Test
The manual test checks for hidden failures of components which the AADvance controller alarms
cannot reveal. To perform the manual test do the following:
Transition each digital input to its opposite state and then back to its current state.
Subject each analogue input to its full range (minimum to maximum) and check
accuracy.
At the same time, check each output operates as expected. Use the application
software to force any outputs which cannot be seen to operate.
Carry out a manual test to exercise every input and output.
Vista de pagina 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 95 96

Comentarios a estos manuales

Sin comentarios