32 Rockwell Automation Publication 1756-UM105E-EN-E - October 2012
Chapter 5 Use the Command Line
Entry Description
Version Version of the script file.
AbortOnFail When flashing a device failed:
0 = continue flashing the remaining devices.
1 = stop flashing the remaining devices.
SkipOnFirmwareMatch If a device to flash already has the matching firmware as stated in the script:
0 = do not skip flashing the device.
1 = skip flashing the device.
NumberDevices Flash the first # of devices in this script file, begin with [Device1].
SilentMode 0 = ControlFLASH console window appears on screen and shows the flash progress.
1 = ControlFLASH console window does not appear on screen.
You will not receive any flash status feedback.
MultiFlash 0 = flash only one device at a time.
1 = flash up to five devices concurrently.
Catalog Catalog number of device as registered with the current installed ControlFLASH software. To identify installed kits, refer to the GUI version of
ControlFLASH software.
For example: 1756-L63/A
Revision Firmware revision you need to flash the device to. This revision must be registered for this device with the current install of the ControlFLASH
software. To identify installed kits, refer to the GUI revision of ControlFLASH software.
For example: 16.23
Path FactoryTalk RSLinx path to the target device.
AB_PCIC-1 2 2 1 7
|_______| | | | |___Node address
| | | |_____Backplane
| | |__ ____PCICS Communication card address
| |________ControlNet cable address
|____________PCICS driver name
AB_ETH-2,192.168.1.4,1,7
|______| |_______| | |__Node Address
| | |___ Backplane
| |_________IP address
|________________ Ethernet driver name