Chapter 1 Program a Function Block Diagram
Example: When the TIC101AutoReq button is pressed, one-shot latch ProgAutoReq for the PIDE instruction TIC101.
TIC101 is configured with the ProgValueReset input set, so when the PIDE instruction executes, it automatically clears
ProgAutoReq.
To add a sheet to a function block routine:
1. On the Sheet toolbar, click Add Sheet
.
2. In the Description box, type a description of the sheet. Follow the
IEC-1131 naming standard. The description must not be greater than 50
characters.
Use the Language Element toolbar to add a function block element to a routine.
1. On the Language Element toolbar, click the button for the element that
you want to add.
Add a sheet
Add a function block
element
20 Rockwell Automation Publication 1756-PM009E-EN-P - October 2014