Monitored Digital Input Modules
, Type F (T3411F, T3418F)
PD
-
6027
Mar
-
06
25
For additional safety considerations, please refer to the Safety
Considerations section of the Regent User’s Guide.
Specifications
Safetybus Power
0.85 load units
Number of Inputs
16, common power
T3411F
T3418F
Field Power
Voltage, min.:
Voltage, max.:
Current:
24 or 48 Vdc
15 Vdc
80 Vdc
450 mA,
maximum
120 Vac/dc
90 Vac/dc
150 Vac/dc
150 mA,
maximum
Turn
-
On Voltage
(default)
> 12 Vdc
> 51 Vdc
Turn
-
Off Voltage
(default)
< 12 Vdc
< 51 Vdc
Input Current
8.0 mA,
maximum
2.0 mA,
maximum
Turn
-
On Delay
10 msec,
maximum
10 msec,
maximum
Turn
-
Off Delay
10 msec,
maximum
100 msec,
maximum
Over Voltage Protection
Field Power Terminals:
Input Terminals:
100 Vdc
continuous
100 Vdc
continuous,
160 Vdc for
5
seconds
165 Vac
continuous
230 Vac
continuous,
350 Vac for
5
seconds
Heat Dissipation
8.5 Watts, 29
BTUs/hour
10 Watts, 34
BTUs/hour
Fusing
None, external if required
Isolation
2500 volts minimum (field
wiring to control logic)