Rockwell-automation T7444 ICS Regent+Plus AC Digital Output Module 110 Manual de usuario Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 13
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
AC Digital Output Module
(T7444)
12
Industrial Control Services
Specifications
Safetybus Power
0.8 load units
Number of Outputs
16 circuits divided into two
groups of 8 circuits each
Voltage Range
90 to 130 VAC
Frequency Range
47 to 63 Hz
Load Current
2 amps maximum per output
0°
to 50
°
C, derated linearly
to 1 amp at 60
°
C
8 amps maximum per group
of 8 outputs 0
°
to 60
°
C
16 amps maximum per
module 0
°
to 60
°
C
Minimum Load
50 mA
On State Drop
2.0 volts maximum
Surge Current
15 amps, 20 msec
Output Leakage
5 mA maximum
Fusing
One 3 A, 250 V, fast
-
acting
(3AG) per output, front panel
mounted
Turn
-
On Delay
½ AC cycle, maximum
Turn
-
Off Delay
½ AC cycle, maximum
Heat Dissipation
28 Watts, 97 BTUs/hour
Over voltage
Protection
175 VAC, continuous
Isolation
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1
-
8 to output group 9
-
16)
Operating Temperature
0°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13

Comentarios a estos manuales

Sin comentarios