AC Digital Output Module
(T7444)
12
Industrial Control Services
Specifications
16 circuits divided into two
groups of 8 circuits each
2 amps maximum per output
0°
to 50
°
C, derated linearly
to 1 amp at 60
°
C
8 amps maximum per group
of 8 outputs 0
°
to 60
°
C
16 amps maximum per
module 0
°
to 60
°
C
One 3 A, 250 V, fast
-
acting
(3AG) per output, front panel
mounted
2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1
-
8 to output group 9
-
16)
0°
to 60
°
C
(32
°
to 140
°
F)
-
40
°
to 85
°
C
(-
40
°
to 185
°
F)