ICS Regent+Plus
®
PD
-
7025
Industrial Control Services
1
Analog Output Modules
4 to 20 mA
(T7470A)
Issue 1,
March, 06
Analog output modules provide 4 to 20 mA current outputs for
a maximum of eight user loads per module. The module's
triplicated I/O Safetybus interface ensures that no
Regent
system failure will inadvertently affect the output signal, and
that no failure in the module can affect the operation of the
Regent system or other I/O modules in the system.
Features
·
Eight 4 to 20 mA output circuits.
·
High resolution 12
-
bit D/A converter per output.
·
Hot
-
replaceable.
·
Automatic testing of triplicate I/O Safetybus circuits and many
simplex logic circui
ts.
·
Front panel indicators on each module show active/fault and
shutdown status.
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
TÜV certified, Risk Class 5, non
-
interfering.
Module Operation
A block diagram of the analog output module is shown in
Figure
1
.
The processor modules send triplicated write data commands
to the output module over the I/O Safe
tybus. The processors’
addressing data and data write commands are voted by the
module (preventing I/O Safetybus failures upstream from the
Vista de pagina 0
1 2 3 4 5 6 ... 15 16

Indice de contenidos

Pagina 1 - ICS Regent+Plus

ICS Regent+Plus® PD-7025 Industrial Control Services 1 Analog Output Modules 4 to 20 mA (T7470A) Issue 1, March, 06 Analog output modules provide 4

Pagina 2

Analog Output Modules (T7470A) 10 Industrial Control Services Programming Outputs are controlled by writing application programs that solve for ou

Pagina 3 - Front Panel Indicators

Analog Output Modules (T7470A) PD-7025 Mar-06 11 control logic, you maintain the full resolution of the analog output (1 part in 4096) and have a

Pagina 4

Analog Output Modules (T7470A) 12 Industrial Control Services Figure 8). During the calibration steps you will remove the printed circuit board f

Pagina 5

Analog Output Modules (T7470A) PD-7025 Mar-06 13 precision load resistors to the analog outputs. Figure 9 shows the jumper posts to which you sh

Pagina 6 - Important!

Analog Output Modules (T7470A) 14 Industrial Control Services 2. Install the I/O extender module into the slot from which the module was removed.

Pagina 7 - Configuration

Analog Output Modules (T7470A) PD-7025 Mar-06 15 analog output module to the factory for repair or replacement. 14. Calibration is complete. Unp

Pagina 8

Analog Output Modules (T7470A) 16 Industrial Control Services Heat Dissipation 10 Watts, 33 BTUs/hour Operating Temperature 0° to 60° C (32° to 14

Pagina 9

Analog Output Modules (T7470A) 2 Industrial Control Services module from affecting module operation). The voted result is then passed to the I/O

Pagina 10 - Programming

Analog Output Modules (T7470A) PD-7025 Mar-06 3 to return the correct majority-voted result to the processors produces an I/O module error indic

Pagina 11 - Maintenance

Analog Output Modules (T7470A) 4 Industrial Control Services Figure 2. Analog Output Module.

Pagina 12 - Industrial Control Services

Analog Output Modules (T7470A) PD-7025 Mar-06 5 Shutdown Indicator Upon loss of communications with the controller, output modules enter either

Pagina 13

Analog Output Modules (T7470A) 6 Industrial Control Services For high integrity applications requiring fail-safe or fault tolerant analog outputs

Pagina 14

Analog Output Modules (T7470A) PD-7025 Mar-06 7 Figure 4. Installing Slot Keys. Configuration Each output module is configured using the WIN

Pagina 15 - Specifications

Analog Output Modules (T7470A) 8 Industrial Control Services 1) Set the Module Type: Position the cursor on the module slot you wish to define.

Pagina 16

Analog Output Modules (T7470A) PD-7025 Mar-06 9 Figure 6. Defining an Analog Output Point. Name Also called the tag name, this is the name use