Trusted
TM
Module T8431
Issue 16 Sep 11 PD-T8431 16
OEM Parameter Description Notes
TICS_CHASSIS The number of the
TrustedTM Chassis
where the primary I/O
module is installed
The TrustedTM Controller Chassis is 1, and
TrustedTM Expander Chassis are 2 to 15
TICS_SLOT The slot number in the
chassis where the
primary I/O module is
installed
The I/O module slots in the TrustedTM
Controller chassis are numbered from 1 to 8.
The I/O Module slots in the TrustedTM Expander
Chassis are numbered from 1 to 12
Table 4 OEM Parameters
3.2.1. Rack 1: THRSHIN
This board allows the current thresholds for an analogue input channel to be read by the application,
under control of the THRSHOUT board (see section 3.2.4).
Channel Description
1 Channel number being read. Range 0 to
41.
2 States 2 > 1 falling threshold
3 States 1 > 2 rising threshold
4 States 3 > 2 falling threshold
5 States 2 > 3 rising threshold
6 States 4 > 3 falling threshold
7 States 3 > 4 rising threshold
8 States 5 > 4 falling threshold
9 States 4 > 5 rising threshold
Table 5 Rack 1: Threshold input descriptions
THRSHIN reads in the module threshold values controlled by THRSHOUT in Rack 4. See Table 1 for a
graphical representation of the states and thresholds.