Trusted
TM
Module T8448
Issue 14 Apr 10 PD-T8448 27
3.2.7. Rack 7: HKEEPING
Description
Channel
FCR Units (Full Scale Range)
24V2 Field Voltage -32768 32767 mV
Internal supply voltage (post regulator) -32768 32767 mV
Internal supply current (post regulator) -32768 32767 mA
Output voltage (post isolation) -32768 32767 mV
24V1 Field Voltage -32768 32767 mV
HIU Board Temperature
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
Front Panel Load Current -32768 32767 mA
SmartSlot Link Voltage -32768 32767 mV
FIU Power Group 1 Field Supply Voltage -32768 32767 mV
FIU Board Temperature, Group 1
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
FIU Power Group 2 Field Supply Voltage -32768 32767 mV
FIU Board Temperature, Group 2
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
FIU Power Group 3 Field Supply Voltage -32768 32767 mV
FIU Board Temperature, Group 3
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
FIU Power Group 4 Field Supply Voltage -32768 32767 mV
FIU Board Temperature, Group 4
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
FIU Power Group 5 Field Supply Voltage -32768 32767 mV
FIU Board Temperature, Group 5
( Note: Temperature, ºC = input value / 256 )
-32768 32767 -
Diagnostic error code
Table 13 Rack 7: Housekeeping descriptions